The Role of Building Sciences in Predictive Maintenance Programs
Phillip C. McMullan
Thermo-Scan Inspections, Carmel, Indiana
ABSTRACT
Following California’s lead, Congress has indicated plans to introduce legislation to require EPA to set national
guidelines for what levels of toxic mold (stachybotrys spp.) constitute a “health risk”. Best’s Review, an insurance
industry publication, recently reported at a national mo ld symposium, sponsored by the Property Loss Research
Bureau, that attorneys for the insurance industry encouraged insurance companies to pursue subrogation in mold
claims. From claims of health troubles to damage to buildings, mold poses a growing problem.
For over twenty years infrared thermography has been used to diagnose building components. Roofs, walls and
structural components in addition to the electrical and mechanical systems have all been included in the list of uses
for thermal imaging. However, as building sciences have matured and infrared cameras, also known as thermal
imagers have improved, the use of nondestructive thermal imaging to examine the building envelope for potential
mold causing water leaks provides the opportunity to expand the role of predictive maintenance in facilities.
Water intrusion is the most significant factor in building premature deterioration. In addition to contributing to the
growth of mold, water penetration of building materials can reduce insulation effectiveness, corrode metals and
cause the chemical breakdown of many organic materials. Rain penetration is not the only source of moisture;
condensation, ground water and facility processes can all contribute to moisture in the building envelope.
The amount of effort and expense that can be justified to identify and minimize water penetration is changing.
Given that insurance companies intend to purse subrogation in mold claims, the facility manager who fails to
recognize and act upon a water penetration situation may well be held liable for damages.
This paper will detail the procedures of non-destructive evaluation on a variety of buildings and report the findings
of these inspections.
Keywords:
Building Sciences, Building Envelope, IR inspection, IR thermography, Moisture, Mold
1.
INTRODUCTION
If building components are to be incorporated into a facility predictive maintenance program, it is important to
define the scope of the inspections to be performed. For purposes of this paper let us limit our scope to potential
sources for excess moisture or water in facilities. The most common sources are as follows:
~ Roof Leaks ~ HVAC Condensation ~ Plumbing Leaks
~ Construction Defects ~ Production Processes ~ Environmental Factors
Each of these areas is self explanatory perhaps with the exception of environmental factors. Include are floods, site
drainage, high groundwater table and climate. The impact of these environmental factors will vary depending on the
goal of the inspection program. If that goal involves reducing the growth of mold, environmental factors such as
climate play a big part in the program. For example, mold growth is facilitated by heat and humidity. Temperatures
between 68 and 86 degrees Fahrenheit along with relative humidity in excess of sixty percent are factors th at support
mold growth.
Given this information certain production processes or operations, which produce both heat and moisture, should
also be analyzed to determine the extent of inspection and monitoring required to make decisions on moisture
remediation. These additional monitoring efforts would be in addition to or in conjunction with current predictive
maintenance programs. Depending on the construction type and use of a facility, the biggest concern from excessive
moisture can range from structural building damage in a factory setting to sick building syndrome from black mold
(aspergillus variecolor) in school and office buildings.